Lex 50 Amp Terrapin Station II to Locking Receptacle Feed Thru

Item Code: T2-A2-6B1E
$2,623.90
$1,931.88
Please enter a quantity.

Lex 50 Amp Terrapin Station II to Locking Receptacle Feed Thru T2-A2-6B1E

Terrapin Station II Enclosure, 50A 125/250 Inlet and Feed Thru, (6) L520 GFCI Locking Receptacles. The PowerHOUSE™ Terrapin Station II™ Series is Lex Products latest generation of portable power distribution boxes to meet stringent UL, NEC and OSHA requirements for indoor/outdoor applications that feature a heavy duty rubber enclosure for enhanced safety and durability. The Terrapin Station II™ Series meets OHSA standards for open-neutral GFCI protection and circuit overload protection, and is designed to deliver power from electrical panels or portable generators. The box is weather-resistant and ideal for powering events and generator rental applications. Enhanced Safety: Terrapin Station II™ Series portable power distribution boxes are cULus Listed and are TYPE 3R Weather Resistant for safe and reliable use in outdoor environments. Weather resistant open-neutral GFCI modules help to prevent unsafe operating conditions and nuisance tripping while LED indicators provide a visual indicator of status. The Terrapin Station II™ Series sturdy aluminum legs are designed to keep electrical components six inches above ground level to meet NEC regulatory compliance. Unprecedented Durability: The Terrapin Station II™ Series rugged and weather resistant construction enables the box to withstand rough treatment and harsh environments while delivering years of trouble-free performance. The heavy duty molded rubber enclosure and lid are fully insulated and resistant to shock, impact and corrosion for enhanced safety, and built to outlast comparable painted steel boxes

Features & Benefits

  • Meets UL, NEC and OSHA requirements for events and generator rental
  • Meets OSHA Regulation 20 Part 1926, Subpart K standards for open-neutral GFCI protection for enhanced safety
  • Heavy duty molded rubber enclosure is fully insulated and resistant to shock, impact and corrosion for years of trouble-free service versus painted metal
  • Thermal magnetic circuit breakers are located under a heavy duty rubber, waterproof, self-closing lid for enhanced breaker protection
  • Weather resistant GFCI protection helps to prevent unsafe operating conditions and nuisance tripping
  • GFCI module possesses LED beacon to indicate device status
  • Locking receptacles provide secure connections that prevent accidental separation
  • cULus Listed and TYPE 3R Rainproof for outdoor use
  • Feed thru feature allows multiple boxes to be placed along one feed
  • Spring-loaded covers protect receptacles and inlets from dirt and moisture intrusion
  • Lightweight and compact for easy portability and storage
  • Heavy-duty aluminum legs position the box at the NEC regulatory height of 6 inches while allowing for storage and transport stacking
  • Molded handle enhances portability while improving stackability of multiple units

Markets Served

  • Electrical Distribution, Maintenance, Shipbuilding, Generator Rental, Construction, Outdoor Events, Shelters

Specs

  • Rating: 50 Amp, Double-phase (H,H,N,G), 3-pole, 4-wire, 125/250Y VAC, 60 Hz
  • Environmental Rating: NEMA Type 3R (Weather Resistant)
  • Input: (1) California Style CS63, 50 Amp, 3-pole, 4-wire, 125/250 VAC, locking inlet, cover door, panel mount
  • Feed Thru: None
  • Main Breaker: None
  • Output: (6) GFCI open-neutral protected, NEMA L5-20, 20 Amp, Single Phase, 2 Pole, 3 Wire, 125 VAC locking receptacles; (1) NEMA L6-30, 30 Amp, Single Phase, 2 Pole, 3 Wire, 250 VAC locking receptacle
  • Enclosure Type: Terrapin II™
  • Dimensions: 14.25"L x 14.25"W x 17.50"H
  • Weight: 29.0lbs
  • Agency Approval: cULus Listed
Menu
Contact Us